Allowable Ampacities of Not More than Three Insulated Conductors

Rated 0-2000 Volts, 60° To 90°C (140° TO 194°F), In Raceway or Cable or Earth (Directly Buried)
Based on ambient air temperature of 30°C (86°F). 

Size Temperature Rating of Conductor
  60°C
(140°F)
75°C
(167°F)
90°C
(194°)
AWG
kcmil
Types: TW*, UF Types: FEPW*, RH*, RHW*, THHW*, THW*, THWN*, XHHW*, USE*, ZQ* Types: TA, TBS, SA, SIS, FEP*, FEPB*, MI, RHH*, RHW-2, THHN*, THHW*, THW-2, THWN-2, USE-2, XHH, XHHW*, XHHW-2, ZW-2
  Copper
18
16
14
12
10
8
--
--
20*
25
30
40
--
--
20*
25*
35*
50
14
18
25*
30*
40*
55
6
4
3
2
1
55
70
85
95
110
65
85
100
115
130
75
95
110
130
150
1/0
2/0
3/0
4/0
125
145
165
195
150
175
200
230
170
195
225
260
250
300
350
400
500
215
240
260
280
320
255
285
310
335
380
290
320
350
380
430
600
700
750
800
900
355
385
400
410
435
420
460
475
490
520
475
520
535
555
585
1000
1250
1500
1750
2000
455
495
520
545
560
545
590
625
650
665
615
665
705
735
750

Size Temperature Rating of Conductor
  60°C
(140°F)
75°C
(167°F)
90°C
(194°)
AWG
kcmil
Types: TW*, UF* Types: RH*, RHW*, THHW*, THW*, THWN*, XHHW*, USE* Types: TA, TBS, SA, SIS, THHN*, THHW*, THW-2, THWN-2, RHH*, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2
  Aluminum or Copper-Clad Aluminum
--
--
--
12
10
8
--
--
--
20*
25
30
--
--
--
20*
30*
40
--
--
--
25*
35*
45
6
4
3
2
1
40
55
65
75
85
50
65
75
90
100
60
75
85
100
115
1/0
2/0
3/0
4/0
100
115
130
150
120
135
155
180
135
150
175
205
250
300
350
400
500
170
190
210
225
260
205
230
250
270
310
230
255
280
305
350
600
700
750
800
900
285
310
320
330
355
340
375
385
395
425
385
420
435
450
480
1000
1250
1500
1750
2000
375
405
435
455
470
445
485
520
545
560
500
545
585
615
630

*Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with and asterisk (*) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.

Table 310-16 NEC


The information presented within this section has been carefully prepared and is believed to be accurate. Alan Wire Company makes no warranties, expressed or implied, and disclaim any responsibility or liability for loss or damage as a result of the use of this information.