| Size | Temperature Rating of Conductor | ||
| 60°C (140°F) |
75°C (167°F) |
90°C (194°) |
|
| AWG kcmil |
Types: TW*, UF | Types: FEPW*, RH*, RHW*, THHW*, THW*, THWN*, XHHW*, USE*, ZQ* | Types: TA, TBS, SA, SIS, FEP*, FEPB*, MI, RHH*, RHW-2, THHN*, THHW*, THW-2, THWN-2, USE-2, XHH, XHHW*, XHHW-2, ZW-2 |
| Copper | |||
|
18 16 14 12 10 8 |
-- -- 20* 25 30 40 |
-- -- 20* 25* 35* 50 |
14 18 25* 30* 40* 55 |
|
6 4 3 2 1 |
55 70 85 95 110 |
65 85 100 115 130 |
75 95 110 130 150 |
|
1/0 2/0 3/0 4/0 |
125 145 165 195 |
150 175 200 230 |
170 195 225 260 |
|
250 300 350 400 500 |
215 240 260 280 320 |
255 285 310 335 380 |
290 320 350 380 430 |
|
600 700 750 800 900 |
355 385 400 410 435 |
420 460 475 490 520 |
475 520 535 555 585 |
|
1000 1250 1500 1750 2000 |
455 495 520 545 560 |
545 590 625 650 665 |
615 665 705 735 750 |
| Size | Temperature Rating of Conductor | ||
| 60°C (140°F) |
75°C (167°F) |
90°C (194°) |
|
|
AWG kcmil |
Types: TW*, UF* | Types: RH*, RHW*, THHW*, THW*, THWN*, XHHW*, USE* | Types: TA, TBS, SA, SIS, THHN*, THHW*, THW-2, THWN-2, RHH*, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2 |
| Aluminum or Copper-Clad Aluminum | |||
|
-- -- -- 12 10 8 |
-- -- -- 20* 25 30 |
-- -- -- 20* 30* 40 |
-- -- -- 25* 35* 45 |
|
6 4 3 2 1 |
40 55 65 75 85 |
50 65 75 90 100 |
60 75 85 100 115 |
|
1/0 2/0 3/0 4/0 |
100 115 130 150 |
120 135 155 180 |
135 150 175 205 |
|
250 300 350 400 500 |
170 190 210 225 260 |
205 230 250 270 310 |
230 255 280 305 350 |
|
600 700 750 800 900 |
285 310 320 330 355 |
340 375 385 395 425 |
385 420 435 450 480 |
|
1000 1250 1500 1750 2000 |
375 405 435 455 470 |
445 485 520 545 560 |
500 545 585 615 630 |
*Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with and asterisk (*) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.
Table 310-16 NEC