Power Factor Improvement of Induction Motor Loads

When power factor correction capacitors are used, the total corrective KVAR on the load side of the motor controller should not exceed the value required to raise the no-load power factor to unity. Corrective KVAR in excess of this value may cause over excitation that results in high transient voltages, currents and torques that can increase safety hazards to personnel and possibly damage the motor or driven equipment.

Do not connect power factor correction capacitors at motor terminals on elevator motors, multispeed motors, plugging or joggging applications or open transition, wye-delta, auto-transformer starting and some part-winding start motors.

If possible, capacitors should be located at position No. 2 (see diagram, below). This does not change the current flowing through the motor overload protectors. Capacitors should be located at position No. 1 for applications listed in Paragraph No. 2 above. Be sure bus power factor is not increased above 95 percent under all loading conditions to avoid over excitation.


The information presented within this section has been carefully prepared and is believed to be accurate. Alan Wire Company makes no warranties, expressed or implied, and disclaim any responsibility or liability for loss or damage as a result of use of this information.