Service Entrance Style U (SEU) 600V - 8000 Series Aluminum Alloy

Description

For use as to deliver electrical service from the service head to the house meter. Compact stranded 8000 series aluminum alloy conductors. XHHW-2 insulated conductors laid in parallel. Bare conductor strands are helically wound around the two parallel conductors. Glass reinforced tape is applied over the assembly. Gray PVC jacket is extruded over the entire assembly.

Standards & Specifications

  • UL 44 for Type XHHW-2 Conductors
  • UL 854
  • Federal Specification JC-30B NEC
  • 8000 Series AL Alloy
  • Flame Retardant Jacket
  • Sunlight Resistant Jacket
Construction Phase Conductor Stranding Ground Conductor Stranding Nom. Cable O.D. (in) Amp. 90ºC Amp. (Dwelling) Lbs./MFt
6/2c-6g 7 11 .458 x .720 60 - 143
4/2c-4g 7 16 .505 x .811 75 - 198
4/2c-6g 7 11 .502 x .808 75 - 184
2/2c-2g 7 15 .559 x .919 100 100 282
2/2c-4g 7 16 .559 x .919 100 100 259
1/0-2c-1/0g 19 18 .661 x 1.095 135 125 438
1/0-2c-2g 19 14 .647 x 1.095 135 125 387
2/0-2c-2/0g 19 18 .719 x 1.208 150 150 516
2/0-2c-1g 19 14 .702 x 1.190 150 150 467
4/0-2c-4/0g 19 30 .857 x 1.445 205 200 770
4/0-2c-2/0g 19 18 .818 x 1.406 205 200 692

**Ampacity chart per NEC.