Type TC-ER Control Cable M-1/E-2

Description

Alan Wire Type TC-ER Control Cable is intended for use in accordance with Article 336 of ANSI/NFPA 70 National Electrical Code. It is suitable for use in wire ways, trays, channels, conduit and ducts. It is UL Listed for direct burial in wet or dry locations, sunlight resistant and available as Exposed run (ER) for use between cable trays and utilization equipment in accordance with NEC 336.10 (7).

Standards & Specifications

  • 18 AWG thru 10 AWG soft annealed, bare copper per ASTM B3 & ASTM-B787
  • UL 83
  • Flame retardant insulation
  • PVC Rated for use at 90º C dry
  • PVC Rated for use at 75º C wet
  • Gasoline & Oil Resistant II
  • Color coded per method ICEA Method M-1
  • E-2 insulated conductors are twisted together
  • ARRA 2009 Section 1605 “Buy American” Compliant
Conductor      
Size (AWG) Number of Conductors Individual Conductor Stranding Jacket Thickness PVC (Inches) Nominal O.D. (Inches) Approx. Wt./MFt
18 2 Flat* 16 0.045 .189 x .287 35
18 3 16 0.045 0.29 47
18 4 16 0.045 0.31 56
18 5 16 0.045 0.34 66
18 7 16 0.045 0.36 84
16 2 Flat* 16 0.045 .205 x .311 43
16 3 26 0.045 0.32 61
16 4 26 0.045 0.34 74
16 5 26 0.045 0.37 98
16 7 26 0.045 0.41 109
14 2 Flat* 19 0.045 .211 x .320 55
14 3 19 0.045 0.33 72
14 4 19 0.045 0.36 94
14 5 19 0.045 0.40 116
14 7 19 0.045 0.43 147
12 2 Flat* 19 0.045 .225 x .360 74
12 3 19 0.045 0.37 102
12 3 BWG** 19 0.045 0.37 102
12 4 19 0.045 0.41 131
12 5 19 0.045 0.44 162
12 7 19 0.045 0.49 231
10 2 Flat* 19 0.045 .261 x .425 109
10 3 19 0.045 0.45 154
10 3 BWG** 19 0.045 0.45 154
10 4 19 0.060 0.49 197
10 5 19 0.060 0.57 260
10 7 19 0.045 0.66 362
12 3 w/ground 19 0.045 0.39 131
10 3 w/ground 19 0.045 0.45 191

*ER rating only applies to 3 or more insulated conductors. Not applicable to conductor items.