Type TC-ER Control Cable
Type TC-ER Control Cable M-1/E-2
Type TC-ER Control Cable is intended for use in accordance with Article 336 of ANSI/NFPA 70 National Electrical Code. It is suitable for use in wire ways, trays, channels, conduit and ducts. It is UL Listed for direct burial in wet or dry locations, sunlight resistant and available as Exposed run (ER) for use between cable trays and utilization equipment, and Joist Pull (JP) applications in accordance with NEC 336.10 (7).
Standards & Specifications
- 18 AWG thru 10 AWG soft annealed, bare copper per ASTM B3 & ASTM-B787
- UL 83
- Flame retardant insulation
- PVC Rated for use at 90º C dry
- PVC Rated for use at 75º C wet
- Gasoline & Oil Resistant II
- Color coded per method ICEA Method M-1
- E-2 insulated conductors are twisted together
- ARRA 2009 Section 1605 “Buy American” Compliant
Wire Size & Specs
Conductor | ||||||
---|---|---|---|---|---|---|
Size (AWG) | Stranding | No. of Conductors | Individual Conductor Stranding |
Jacket Thickness PVC (Inches) |
Nom. OD (Inches) | Approx Net WT./MFT |
Conductor Size (AWG) 18 |
Stranding 16 |
No. of Conductors 2 Flat | Individual Conductor Stranding 16 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) .1890 x .2870 |
Approx Net WT./MFT 35 |
Conductor Size (AWG) 18 |
Stranding 16 |
No. of Conductors 3 | Individual Conductor Stranding 16 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) 0.290 |
Approx Net WT./MFT 47 |
Conductor Size (AWG) 18 |
Stranding 16 |
No. of Conductors 4 | Individual Conductor Stranding 16 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) 0.310 |
Approx Net WT./MFT 56 |
Conductor Size (AWG) 18 |
Stranding 16 |
No. of Conductors 5 | Individual Conductor Stranding 16 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) 0.340 |
Approx Net WT./MFT 66 |
Conductor Size (AWG) 18 |
Stranding 16 |
No. of Conductors 7 | Individual Conductor Stranding 16 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) 0.360 |
Approx Net WT./MFT 84 |
Conductor Size (AWG) 16 |
Stranding 26 |
No. of Conductors 2 Flat | Individual Conductor Stranding 16 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 43 |
Conductor Size (AWG) 16 |
Stranding 26 |
No. of Conductors 3 | Individual Conductor Stranding 26 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 61 |
Conductor Size (AWG) 16 |
Stranding 26 |
No. of Conductors 4 | Individual Conductor Stranding 26 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 74 |
Conductor Size (AWG) 16 |
Stranding 26 |
No. of Conductors 5 | Individual Conductor Stranding 26 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 98 |
Conductor Size (AWG) 16 |
Stranding 26 |
No. of Conductors 7 | Individual Conductor Stranding 26 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 109 |
Conductor Size (AWG) 14 |
Stranding 19 |
No. of Conductors 2 Flat | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 55 |
Conductor Size (AWG) 14 |
Stranding 19 |
No. of Conductors 3 | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 72 |
Conductor Size (AWG) 14 |
Stranding 19 |
No. of Conductors 4 | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 94 |
Conductor Size (AWG) 14 |
Stranding 19 |
No. of Conductors 5 | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 116 |
Conductor Size (AWG) 14 |
Stranding 19 |
No. of Conductors 7 | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 147 |
Conductor Size (AWG) 12 |
Stranding 19 |
No. of Conductors 2 Flat | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 74 |
Conductor Size (AWG) 12 |
Stranding 19 |
No. of Conductors 3 | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 102 |
Conductor Size (AWG) 12 |
Stranding 19 |
No. of Conductors 3 BWG | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 102 |
Conductor Size (AWG) 12 |
Stranding 19 |
No. of Conductors 4 | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 131 |
Conductor Size (AWG) 12 |
Stranding 19 |
No. of Conductors 5 | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 162 |
Conductor Size (AWG) 12 |
Stranding 19 |
No. of Conductors 7 | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 231 |
Conductor Size (AWG) 10 |
Stranding 19 |
No. of Conductors 2 Flat | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 109 |
Conductor Size (AWG) 10 |
Stranding 19 |
No. of Conductors 3 | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 154 |
Conductor Size (AWG) 10 |
Stranding 19 |
No. of Conductors 3 BWG | Individual Conductor Stranding 19 | Jacket Thickness PVC (Inches) 0.045 |
Nom. OD (Inches) N/A |
Approx Net WT./MFT 154 |
*ER rating only applies to 3 or more insulated conductors. Not applicable to conductor items. | ||||||
**Conductors are Black, White, and Green. |