Type TC-ER 600 Volt Power Cable M-1/E-2
Type TC-ER-JP Control Cable is intended for use in accordance with Article 336 of ANSI /NFPA 70 National Electrical Code.
Alan Wire Type TC-ER-JP Control Cable is intended for use in accordance with Article 336 of ANSI /NFPA 70 National Electrical Code. Suitable for use in wire ways, trays, channels, conduit, ducts, and Class I Division II Hazardous Locations. It is UL listed for direct burial in wet or dry locations, or in areas exposed to chemicals or oils. Sunlight resistant and available as Exposed run (ER) for use between cable trays and utilization equipment, and Joist Pull (JP) applications in accordance with NEC 336.10 (7).
Standards & Specifications
- 18 AWG Thru 10 AWG Soft-Annealed, Bare Copper per ASTM B3 & ASTM-B787
- UL 83
- Flame-Retardant Insulation
- PVC Rated 90°C Dry/75°C Wet
- Color Coded per Method ICEA Method M-1
- Finished Cable Meets Specification UL 1277
- ARRA 2009 Section 1605 “Buy American” Compliant
- Constructed with Nylon Rip-Cord
Wire Size & Specs
Conductor | ||||||
---|---|---|---|---|---|---|
Size (AWG) | Number of Conductors |
Individual Conductor Stranding |
Jacket Thickness PVC(Inches) |
Nominal O.D (Inches) |
Approx Net WT./MFT | |
Conductor Size (AWG) 18 |
Number of Conductors 2 Flat* | Individual Conductor Stranding 16 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) .189 x .287 |
Approx Net WT./MFT 35 | |
Conductor Size (AWG) 18 |
Number of Conductors 3 | Individual Conductor Stranding 16 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.290 |
Approx Net WT./MFT 47 | |
Conductor Size (AWG) 18 |
Number of Conductors 4 | Individual Conductor Stranding 16 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.310 |
Approx Net WT./MFT 56 | |
Conductor Size (AWG) 18 |
Number of Conductors 5 | Individual Conductor Stranding 16 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.340 |
Approx Net WT./MFT 66 | |
Conductor Size (AWG) 18 |
Number of Conductors 7 | Individual Conductor Stranding 16 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.360 |
Approx Net WT./MFT 84 | |
Conductor Size (AWG) 16 |
Number of Conductors 2 Flat* | Individual Conductor Stranding 16 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) .205 x .311 |
Approx Net WT./MFT 43 | |
Conductor Size (AWG) 16 |
Number of Conductors 3 | Individual Conductor Stranding 26 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.32 |
Approx Net WT./MFT 61 | |
Conductor Size (AWG) 16 |
Number of Conductors 4 | Individual Conductor Stranding 26 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.34 |
Approx Net WT./MFT 74 | |
Conductor Size (AWG) 16 |
Number of Conductors 5 | Individual Conductor Stranding 26 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.37 |
Approx Net WT./MFT 98 | |
Conductor Size (AWG) 16 |
Number of Conductors 7 | Individual Conductor Stranding 26 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.41 |
Approx Net WT./MFT 109 | |
Conductor Size (AWG) 14 |
Number of Conductors 2 Flat* | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) .211 x .320 |
Approx Net WT./MFT 55 | |
Conductor Size (AWG) 14 |
Number of Conductors 3 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.33 |
Approx Net WT./MFT 72 | |
Conductor Size (AWG) 14 |
Number of Conductors 4 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.36 |
Approx Net WT./MFT 94 | |
Conductor Size (AWG) 14 |
Number of Conductors 5 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.40 |
Approx Net WT./MFT 116 | |
Conductor Size (AWG) 14 |
Number of Conductors 7 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.43 |
Approx Net WT./MFT 147 | |
Conductor Size (AWG) 12 |
Number of Conductors 2 Flat* | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) .225 x .360 |
Approx Net WT./MFT 74 | |
Conductor Size (AWG) 12 |
Number of Conductors 3 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.37 |
Approx Net WT./MFT 102 | |
Conductor Size (AWG) 12 |
Number of Conductors 3 BWG** | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.37 |
Approx Net WT./MFT 102 | |
Conductor Size (AWG) 12 |
Number of Conductors 4 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.41 |
Approx Net WT./MFT 131 | |
Conductor Size (AWG) 12 |
Number of Conductors 5 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.44 |
Approx Net WT./MFT 162 | |
Conductor Size (AWG) 12 |
Number of Conductors 7 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.49 |
Approx Net WT./MFT 231 | |
Conductor Size (AWG) 10 |
Number of Conductors 2 Flat* | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) .261 x .425 |
Approx Net WT./MFT 109 | |
Conductor Size (AWG) 10 |
Number of Conductors 3 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.45 |
Approx Net WT./MFT 154 | |
Conductor Size (AWG) 10 |
Number of Conductors 3 BWG** | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.45 |
Approx Net WT./MFT 154 | |
Conductor Size (AWG) 10 |
Number of Conductors 4 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.060 |
Nominal O.D (Inches) 0.49 |
Approx Net WT./MFT 197 | |
Conductor Size (AWG) 10 |
Number of Conductors 5 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.060 |
Nominal O.D (Inches) 0.57 |
Approx Net WT./MFT 260 | |
Conductor Size (AWG) 10 |
Number of Conductors 7 | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.66 |
Approx Net WT./MFT 363 | |
Conductor Size (AWG) 12 |
Number of Conductors 3 w/ ground | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.39 |
Approx Net WT./MFT 131 | |
Conductor Size (AWG) 10 |
Number of Conductors 3 w/ ground | Individual Conductor Stranding 19 | Nominal Jacket Thickness(Inches) 0.045 |
Nominal O.D (Inches) 0.45 |
Approx Net WT./MFT 191 | |
*ER rating only applies to 3 or more insulated conductors. Not applicable to conductor items. **Conductors are Black, White, and Green. |